The Concern
The homeowner contacted StructSolve to evaluate several related concerns at a residential garage in Des Moines, Iowa. The primary issues involved visible garage foundation movement, a cracked and uneven concrete slab, possible termite damage, and signs that drainage conditions may have been contributing to ongoing soil movement near the structure.
The concern was not limited to one isolated crack. The source report described movement across the garage slab and foundation area, including elevation variation, visible displacement between masonry blocks, gaps between the garage slab and original foundation, deterioration, erosion, and framing that had moved out of plumb. Because these conditions affected the garage foundation and portions of the structural system, the property owner needed engineering documentation rather than only a contractor repair opinion.
Why StructSolve Was Contacted
StructSolve was asked to provide an engineering evaluation of readily observable and accessible structural components. The evaluation focused on the garage foundation, suspected insect-related deterioration, drainage patterns, and evidence of settlement. The report did not include destructive testing, removal of finishes, or evaluation of concealed elements, so the findings were based on what could be observed during the site visit.
This type of project aligns with an Observation & Report because the evaluation addressed multiple related structural and site conditions. StructSolve reviewed the garage slab, foundation movement, exterior drainage, retaining wall conditions, driveway slope, soil grading, and the area where deterioration had been questioned.
What StructSolve Observed
StructSolve documented a significant crack in the garage concrete slab and measured slab elevation variation through much of the structure. The report noted that the south end of the garage was approximately two inches lower than the center, indicating differential movement. The observed movement was described as consistent with soil migration under the south side of the garage.
The exterior review identified additional signs of foundation movement, including cracking, displacement between masonry blocks, large gaps between the slab and original foundation, and areas of foundation deterioration and erosion. These conditions had contributed to a measurable lean in the garage and had placed portions of the framing out of plumb.
The evaluation also reviewed site drainage conditions. A downspout was missing an extension, which may have allowed roof runoff to discharge too close to the foundation. The gutter system showed staining consistent with possible clogging or defective gutter guards. The driveway was measured as sloping toward the garage foundation, and a depression was noted near a garage door opening. Soil along one side of the structure also sloped toward the foundation, which may have allowed water to accumulate near the garage if not corrected.
The retaining wall showed outward displacement and deterioration consistent with long-term soil movement. This was generally consistent with the settlement observed along the garage area.
StructSolve also reviewed a location that had been identified as possible termite damage. The observed deterioration was found to be more consistent with moisture-related deterioration than insect damage based on the visible conditions documented in the report.
Engineering Assessment
The report described the garage as being in poor structural condition due to the extent of settlement and the resulting distortion of the structural system. StructSolve noted that no evidence was observed indicating an imminent collapse condition at the time of the evaluation, while also explaining that the measured lean reduced the garage structure’s reserve capacity to resist future gravity and lateral loading.
The assessment connected the observed foundation movement to site conditions that could contribute to continued soil migration and settlement. Poor exterior drainage, improper grading, driveway drainage toward the garage, and localized water discharge near the foundation were all identified as conditions that should be addressed to reduce the potential for additional movement.
Because the evaluation was non-invasive, the report was limited to visible and accessible conditions. Concealed deterioration, hidden foundation conditions, and conditions behind finishes were not part of the scope.
Remedial Actions
StructSolve recommended continued monitoring of the garage for evidence of ongoing settlement. Specific items to watch included increased leaning, widening cracks, distortion of framing members, and difficulty operating the overhead door. If movement continued, the report stated that reconstruction of the garage should be considered.
The report also explained that immediate replacement was not considered necessary based solely on the visible conditions observed during the evaluation. However, the structure had experienced enough settlement that repair might not be economically practical depending on the owner’s long-term plans for the garage.
For continued use of the garage in its current condition, the report stated that supplemental knee braces between wall framing and roof framing could be considered to increase relative lateral stiffness. The recommendation was limited in scope: braces may reduce racking of the framing, but they would not correct the existing lean, restore lost foundation support, or prevent future settlement.
Drainage improvements were identified as a priority. The missing downspout extension should be corrected so roof runoff is discharged away from the foundation. The gutter and gutter guard systems should be cleaned, assessed, and repaired or replaced as needed. Soil adjacent to the structure should be regraded to slope away from the foundation, and the driveway depression near the garage opening should be repaired or resurfaced to reduce ponding and drainage toward the foundation.
Outcome
The structural report helped the property owner understand how the observed garage settlement, drainage deficiencies, slab movement, retaining wall deterioration, and moisture-related trim damage related to one another. It also provided a practical order of next steps: prioritize drainage corrections, monitor the garage for continued movement, and have the garage foundation and framing reviewed by a qualified contractor to evaluate repair versus replacement options.
The deliverable did not document completed repairs or claim that the structure had been restored. Instead, it clarified the visible conditions, identified likely contributing factors, and outlined recommendations the property owner could use for planning and decision-making.